TIC-DIN-MODBUS is a device which can demodulate Linky informations TIC (or old french counter meter). It provides informations with RS845 Modbus RTU interface.
You can with Webpage:
- Add specific managed TIC command
- Configure Modbus parameter
- Configure WiFi SSID/Password
- Add User/Password for HTTP webpage
- See ModBus with mapping table and Network status
- Update the device
TIC-DIN-MODBUS is compatible with historic and standard mode. The mode is detected automaticaly.
TIC-DIN-MODBUS est disponible en boutique : https://lixee.fr/teleinformation/39-tic-din-modbus-rtu-rs485-3770014375186.html
TIC-DIN-MODBUS use a DIN rail module 1U. It is based on ESP32-C3 module and a MAX485 chip for the RS485 interface
- VIN (5 - 12VDC)
- A (+)
- B (-)
- GND
- I1
- I2
With the webpage config, go to "Tools" then "Update" :
Then, click on "Choose File...", then select the binary file then click on "Update" and that's all
In this case, TIC-DIN-MODBUS can't demodulate the counter meter or there are too errors. It is possible that this case can appear 10-15 seconds after resetting due to the mode detection.
In this case, All it's OK. The device demodulate correctly the counter meter.
- SSID : LIXEETIC-XXXX (editable)
- password : adminXXXX (editable - must be 8 characters) PS : XXXX is the end of the @MAC
Please open a browser with this IP address : http://192.168.4.1 to connect to the device
- id master : 1 (editable)
- speed (bauds) : 9600 (editable)
- Data bits : 8
- Stop bits : 1
- Parity : none
| Mode | command | @registry |
|---|---|---|
| Historique | ADCO | 300-303 |
| Historique | OPTARIF | 2000-2099 |
| Historique | BASE | 1004-1007 |
| Historique | ISOUSC | 1399 |
| Historique | HCHC | 1004-1007 |
| Historique | HCHP | 1008-1011 |
| Historique | EJPHN | 1004-1007 |
| Historique | EJPHPM | 1008-1011 |
| Historique | BBRHCJB | 1004-1007 |
| Historique | BBRHPJB | 1008-1011 |
| Historique | BBRHCJW | 1012-1015 |
| Historique | BBRHPJW | 1016-1019 |
| Historique | BBRHCJR | 1020-1023 |
| Historique | BBRHPJR | 1024-1027 |
| Historique | IINST1 | 1320 |
| Historique | IINST2 | 1321 |
| Historique | IINST3 | 1322 |
| Historique | IINST | 1320 |
| Historique | IMAX1 | 1600 |
| Historique | IMAX2 | 1601 |
| Historique | IMAX3 | 1602 |
| Historique | IMAX | 1600 |
| Historique | PMAX | 1361-1364 |
| Historique | PAPP | 1329-1332 |
| Historique | ADPS | 1700 |
| Historique | ADIR1 | 1603 |
| Historique | ADIR2 | 1604 |
| Historique | ADIR3 | 1605 |
| Historique | PEJP | 1606 |
| Historique | PTEC | 2200-2299 |
| Historique | HHPHC | 5000-5099 |
| Standard | ADSC | 300-303 |
| Standard | NGTF | 2000-2099 |
| Standard | LTARF | 2100-2199 |
| Standard | DATE | 3000-3099 |
| Standard | STGE | 4000-4099 |
| Standard | EAST | 1000-1003 |
| Standard | EASF01 | 1004-1007 |
| Standard | EASF02 | 1008-1011 |
| Standard | EASF03 | 1012-1015 |
| Standard | EASF04 | 1016-1019 |
| Standard | EASF05 | 1020-1023 |
| Standard | EASF06 | 1024-1027 |
| Standard | EASF07 | 1028-1031 |
| Standard | EASF08 | 1032-1035 |
| Standard | EASF09 | 1036-1039 |
| Standard | EASF10 | 1040-1043 |
| Standard | EASD01 | 1100-1103 |
| Standard | EASD02 | 1104-1107 |
| Standard | EASD03 | 1108-1111 |
| Standard | EASD04 | 1112-1115 |
| Standard | EAIT | 1200-1203 |
| Standard | ERQ1 | 1300-1303 |
| Standard | ERQ2 | 1304-1307 |
| Standard | ERQ3 | 1308-1311 |
| Standard | ERQ4 | 1312-1315 |
| Standard | IRMS1 | 1320 |
| Standard | IRMS2 | 1321 |
| Standard | IRMS3 | 1322 |
| Standard | URMS1 | 1323 |
| Standard | URMS2 | 1324 |
| Standard | URMS3 | 1325 |
| Standard | PREF | 1399 |
| Standard | STGE | |
| Standard | PCOUP | 1398 |
| Standard | SINSTI | 1400-1403 |
| Standard | SMAXIN-1 | 1404-1407 |
| Standard | SMAXIN | 1408-1411 |
| Standard | CCASN-1 | 1500-1503 |
| Standard | CCASN | 1504-1507 |
| Standard | CCAIN-1 | 1412-1415 |
| Standard | CCAIN | 1416-1419 |
| Standard | UMOY1 | 1326 |
| Standard | UMOY2 | 1327 |
| Standard | UMOY3 | 1328 |
| Standard | SINSTS1 | 1329-1332 |
| Standard | SINSTS2 | 1333-1336 |
| Standard | SINSTS3 | 1337-1340 |
| Standard | SINSTS | 1329-1332 |
| Standard | SMAXSN-1 | 1345-1348 |
| Standard | SMAXSN1-1 | 1345-1348 |
| Standard | SMAXSN2-1 | 1353-1356 |
| Standard | SMAXSN3-1 | 1357-1360 |
| Standard | SMAXSN1 | 1361-1364 |
| Standard | SMAXSN2 | 1365-1368 |
| Standard | SMAXSN3 | 1369-1372 |
| Standard | SMAXSN | 1361-1364 |
| Standard | MSG1 | 6000-6099 |
| Standard | MSG2 | 6100-6199 |
| Standard | PRM | 7000-7099 |
With the webpage, you can add new TIC command with ModBus registry address.
Go to "Tools" and "ModBus" button then click on "registres_spec.json"
Then you get a Json file like :
{
"historique":[{
"reg":1,
"command":"xxxx",
"size":4,
"type":"numeric"
}
],
"standard":[{
"reg":1,
"command":"xxxx",
"size":4,
"type":"string"
}
]
}With this file, you can add new TIC command with historic or standard mode.
- reg : Registry address
- command : TIC command (for ex : DATECOUR)
- size : max size value of the command
- type : value type (only "string" or "numeric"
Click to "save" to validate
- Fix Serial speed change between historic and standard mode
- fix auto-detection speed
- Initial version